GENERAL DESCRIPTION: Larsen's Architectural Series is a traditional, value-added line of recessed, semi-recessed, and surface mounted fire extinguisher cabinets. These units are designed for all types of buildings and are equipped with the conventional door styles such as those pictured below. The standard door and trim material is steel, and optional materials include both aluminum and stainless steel. All doors are 1/2 inch thick and open 180 degrees. All doors have a satin finish pull handle with a self-adjusting roller catch; and a continuous piano hinge constructed of material which matches the door and trim.

BOX SPECIFICATION: All recessed and semi-recessed cabinets and surface-mounted steel cabinets have a heavy gauge, white baked enamel box. Surface-mounted cabinets with aluminum door and trim have a box constructed entirely of clear or color anodized aluminum. Surface-mounted cabinets with stainless steel door and trim have a box constructed entirely of 304 stainless steel with #4 finish.

TRIM AND DOOR SPECIFICATION: Steel trims and doors are one piece, constructed of cold-rolled steel with a standard finish of white baked acrylic enamel, which can be used as either a finish or prime coat. Aluminum trims are constructed of extruded or fabricated aluminum and all corners are mitered. Aluminum is the recommended material for applications in salt air and other corrosion prone environments.

Clear satin anodized finish is standard for all trims and doors, and a wide selection of optional color anodized finishes is available. To specify aluminum trim and door, use the prefix AL before the cabinet model number. Stainless steel trims and doors are one piece, constructed of #4 finish, 304 stainless steel. To specify stainless steel trim and door, use the prefix SS before the cabinet model number. All steel and stainless steel doors have a tubular, hollow-metal design. A sample of door and trim materials is pictured.

TO SPECIFY THE ARCHITECTURAL SERIES:

  • Use the appropriate prefix for the trim and door material. If steel - no prefix is required.
    If aluminum - use AL. If stainless steel - use SS.
  • Select the required model number from the dimension chart under the Table button.
  • Select the door style from the pictures on this screen.
  • Other options: die cut lettering, special finishes (paint, color anodized aluminum or #8 stainless steel), Vigilante Alarm, "FIRE" Handle, Recessed Handle (see the "Exclusive Options for Extinguisher Cabinets" profile).

ARCHITECTURAL SERIES DOOR STYLES (TRIM AND DOOR MATERIAL)
FULL CLEAR ACRYLIC DOOR* (BRONZE ANODIZED ALUMINUM)
FULL CLEAR
ACRYLIC DOOR*
(BRONZE ANODIZED ALUMINUM)
HORIZONTAL DUO CLEAR ACRYLIC DOOR* (WHITE BAKED ENAMEL)
HORIZONTAL DUO
CLEAR ACRYLIC DOOR* (WHITE BAKED ENAMEL)
VERTICAL DUO CLEAR ACRYLIC DOOR*(#4 STAINLESS STEEL)
VERTICAL DUO CLEAR ACRYLIC DOOR*
(#4 STAINLESS STEEL)
FULL CLEAR ACRYLIC DOOR WITH LARSEN-LOC®* (CLEAR ANODIZED ALUMINUM)
FULL CLEAR
ACRYLIC DOOR
WITH LARSEN-LOC®* (CLEAR ANODIZED ALUMINUM)
SOLID DOOR (#4 STAINLESS STEEL)
SOLID DOOR
(#4 STAINLESS STEEL)
SOLID DOOR WITH VERTICAL ENGRAVED LETTERS (#8 STAINLESS STEEL)
SOLID DOOR
WITH VERTICAL
ENGRAVED LETTERS
(#8 STAINLESS STEEL)
SOLID DOOR WITH LARSEN-LOC®* (#4 STAINLESS STEEL)
SOLID DOOR WITH LARSEN-LOC®*
(#4 STAINLESS STEEL)
SOLID DOOR WITH RECESSED HANDLE AND BLACK VERTICAL DIE-CUT LETTERS (WHITE BAKED ENAMEL STEEL)
SOLID DOOR WITH
RECESSED HANDLE AND
BLACK VERTICAL DIE-CUT LETTERS (WHITE BAKED ENAMEL STEEL)
VERTICAL DUO CLEAR ACRYLIC DOOR WITH LARSEN-LOC®* (#4 STAINLESS STEEL)
VERTICAL DUO CLEAR
ACRYLIC DOOR
WITH LARSEN-LOC®*
(#4 STAINLESS STEEL)
HORIZONTAL DUO CLEAR ACRYLIC DOOR WITH LARSEN-LOC®*
HORIZONTAL DUO CLEAR ACRYLIC DOOR WITH LARSEN-LOC®*

*Clear acrylic is standard. These doors also can be glazed with tempered safety glass, clear wire glass, laminated safety glass,
bronze or gray acrylic.

THE LARSEN-LOC® DOOR STYLE OPTION:

In 1997, Larsen's was proud to present the industry with a truly innovative and contemporary approach to the option of equipping a cabinet door with a cylinder lock. The LARSEN-LOC® was the first system to provide the protection of a locked cabinet without requiring the breaking of glass to gain access to the fire extinguisher or other life safety contents. By specifying the LARSEN-LOC®, access to a locked cabinet became totally independent of the desired door style and glazing. Cabinet access for the first time no longer required destruction of the glazing.

Since there is no glass to break, the specification of LARSEN-LOC® has quickly replaced the traditional "Break Glass" door description. This steel cam lock-based design clearly has created a new industry standard. During an emergency, it permits opening of the cabinet door by pulling sharply on the handle. Yet the LARSEN-LOC® also is secure enough to deter the vandalism typically associated with standard pull handles. To specify a built-in cylinder lock system that genuinely optimizes protection and safety, designate the LARSEN-LOC® in combination with any desired door style and glazing option (see below for the options.) The Solid Door with LARSEN-LOC® also can be specified as an Institutional Door (emergency access only with a key) by deleting the pull handle and decal.

LARSEN-LOC® ADVANTAGES:

  • Specific instructions and uncomplicated design provide the best deterrent against tampering or unauthorized cabinet entry when compared to those systems that still require destruction of the glazing.
  • Factory applied lettering reads: "IN CASE OF FIRE ONLY - PULL FIRMLY ON HANDLE".
  • During an emergency, it saves critical seconds by eliminating the two stage process of first breaking the glass and then reaching into the cabinet around the broken glass to operate the locking mechanism.
  • Combines the option to lock the cabinet with the flexibility to specify whatever door style and glazing options are desired.
  • Eliminates the need for the traditional glass breaker bar - or even more importantly, if the breaker is missing, the dangerous use of substitutes such as hands, shoes, etc.
  • Eliminates the need for other unproven and expensive glass breaking methods currently on the market.

DIMENSIONS
Model
Number
Trim Style
and
Projection
Inside Box
Dimensions
H x W x D
Outside Trim
Dimensions
H x W**
Rough
Opening
H x W x D
Complies
With
ADA?
Recommended
Extinguisher
Capacity
  2409-R1 Rec. 5/16 24 x 9½ x 5* 27½ x 13 25 x 10½ x 5¼ YES MP2½,MP5,
MP5-A,DC2½,
DC5,HT2½,HT5
FS 2409-R1 Rec. 5/16 24 x 9½ x 5* 27½ x 13 261/8 x 115/8 x 61/8 YES
  2409-5R Semi-Rec. 1½ 24 x 9½ x 5* 27½ x 13 25 x 10½ x 4 YES
FS 2409-5R Semi-Rec. 1½ 24 x 9½ x 5* 27½ x 13 261/8 x 115/8 x 47/8 YES
  2409-R3 Semi-Rec. 2½ 24 x 9½ x 5* 27½ x 13 25 x 10½ x 3 YES
FS 2409-R3 Semi-Rec. 2½ 24 x 9½ x 5* 27½ x 13 261/8 x 115/8 x 3¾ YES
  2409-R2 Rec. 5/16 24 x 9½ x 6 27½ x 13 25 x 10½ x 6¼ YES MP2½,MP5,
MP5-A,DC2½,
DC5,MP6,MP10,
DC6,DC10,CD5,
HT2½,HT5
FS 2409-R2 Rec. 5/16 24 x 9½ x 6 27½ x 13 261/8 x 115/8 x 71/8 YES
  2409-R7 Semi-Rec. 1½ 24 x 9½ x 6 27½ x 13 25 x 10½ x 5 YES
FS 2409-R7 Semi-Rec. 1½ 24 x 9½ x 6 27½ x 13 26½ x 115/8 x 57/8 YES
  2409-6R Semi-Rec. 2½ 24 x 9½ x 6 27½ x 13 25 x 10½ x 4 YES
FS 2409-6R Semi-Rec. 2½ 24 x 9½ x 6 27½ x 13 261/8 x 115/8 x 47/8 YES
  2409-RM Semi-Rec. 4½ 24 x 9½ x 6 27½ x 13 25 x 10½ x 2 ADA Height Requirement
FS 2409-RM Semi-Rec. 4½ 24 x 9½ x 6 27½ x 13 261/8 x 115/8 x 27/8 ADA Height Requirement
  2409-RT Trimless 24 x 9½ x 6 -- -- x -- x 6½ YES
  2409-R4 Semi-Rec. 3½ 24 x 9½ x 6 27½ x 13 25 x 10½ x 3 YES
FS 2409-R4 Semi-Rec. 3½ 24 x 9½ x 6 27½ x 13 261/8 x 115/8 x 4 YES
  2409-SM Surface Mtd. 27½ x 13 x 6 27½ x 13 -- ADA Height Requirement
  2409-RA Semi-Rec. 4 24 x 9½ x 6 27½ x 13 25 x 10½ x 2½ ADA Handle Requirement
FS 2409-RA Semi-Rec. 4 24 x 9½ x 6 27½ x 13 261/8 x 115/8 x 33/8 ADA Handle Requirement
  2712-R Rec. 5/16 27 x 12 x 8 30½ x 15½ 28 x 13 x 8¼ YES PW2½,MP20,
DC20,CD10,
WC-6L,
HT11, HT15½
FS 2712-R Rec. 5/16 27 x 12 x 8 30½ x 15½ 291/8 x 141/8 x 91/8 YES
  2712-RK Semi-Rec. 1¼ 27 x 12 x 8 30½ x 15½ 28 x 13 x 7¼ YES
FS 2712-RK Semi-Rec. 1¼ 27 x 12 x 8 30½ x 15½ 291/8 x 141/8 x 81/8 YES
  2712-RL Semi-Rec. 2½ 27 x 12 x 8 30½ x 15½ 28 x 13 x 6 YES
FS 2712-RL Semi-Rec. 2½ 27 x 12 x 8 30½ x 15½ 291/8 x 141/8 x 7 YES
  2712-RM Semi-Rec. 4½ 27 x 12 x 8 30½ x 15½ 28 x 13 x 4 ADA Height Requirement
FS 2712-RM Semi-Rec. 4½ 27 x 12 x 8 30½ x 15½ 291/8 x 141/8 x 47/8 ADA Height Requirement
  2712-RT Trimless 27 x 12 x 8 -- -- x -- x 8½ YES
  2712-SM Surface Mtd. 30½ x 15½ x 8½ 30½ x 15½ -- ADA Height Requirement
  2712-RA Semi-Rec. 4 27 x 12 x 8 30½ x 15½ 28 x 13 x 4½ ADA Handle Requirement
FS 2712-RA Semi-Rec. 4 27 x 12 x 8 30½ x 15½ 291/8 x 141/8 x 53/8 ADA Handle Requirement
  2720-R Rec. 5/16 27 x 20 x 8 30½ x 23½ 28 x 21 x 8¼ YES Two ea. of the
listed: PW2½,
MP10,DC10,
MP20,DC20,CD5,
CD10,WC-6L,
HT11,HT15½
FS 2720-R Rec. 5/16 27 x 20 x 8 30½ x 23½ 291/8 x 221/8 x 91/8 YES
  2720-RK Semi-Rec. 1¼ 27 x 20 x 8 30½ x 23½ 28 x 21 x 7¼ YES
FS 2720-RK Semi-Rec. 1¼ 27 x 20 x 8 30½ x 23½ 291/8 x 221/8 x 81/8 YES
  2720-RL Semi-Rec. 2½ 27 x 20 x 8 30½ x 23½ 28 x 21 x 6 YES
FS 2720-RL Semi-Rec. 2½ 27 x 20 x 8 30½ x 23½ 291/8 x 221/8 x 7 YES
  2720-RM Semi-Rec. 4½ 27 x 20 x 8 30½ x 23½ 28 x 21 x 4 ADA Height Requirement
FS 2720-RM Semi-Rec. 4½ 27 x 20 x 8 30½ x 23½ 291/8 x 221/8 x 47/8 ADA Height Requirement
  2720-RT Trimless 27 x 20 x 8 -- - - x - - x 8½ YES
  2720-SM Surface Mtd. 30½ x 23½ x 8½ 30½ x 23½ -- ADA Height Requirement
  2720-RA Semi-Rec. 4 27 x 20 x 8 30½ x 23½ 28 x 21 x 4½ ADA Handle Requirement
FS 2720-RA Semi-Rec. 4 27 x 20 x 8 30½ x 23½ 291/8 x 221/8 x 53/8 ADA Handle Requirement
  3612-R Rec. 5/16 36 x 12 x 8 39½ x 15½ 37 x 13 x 8¼ YES PW2½,MP20,
DC20,CD10,
WC-6L
FS 3612-R Rec. 5/16 36 x 12 x 8 39½ x 15½ 381/8 x 141/8 x 91/8 YES
  3612-RK Semi-Rec. 1¼ 36 x 12 x 8 39½ x 15½ 37 x 13 x 7¼ YES
FS 3612-RK Semi-Rec. 1¼ 36 x 12 x 8 39½ x 15½ 381/8 x 141/8 x 81/8 YES
  3612-RL Semi-Rec. 2½ 36 x 12 x 8 39½ x 15½ 37 x 13 x 6 YES
FS 3612-RL Semi-Rec. 2½ 36 x 12 x 8 39½ x 15½ 381/8 x 141/8 x 7 YES
  3612-RM Semi-Rec. 4½ 36 x 12 x 8 39½ x 15½ 37 x 13 x 4 ADA Height Requirement
FS 3612-RM Semi-Rec. 4½ 36 x 12 x 8 39½ x 15½ 381/8 x 141/8 x 47/8 ADA Height Requirement
  3612-RT Trimless 36 x 12 x 8 -- - - x - - x 8½ YES
  3612-SM Surface Mtd. 39½ x 15½ x 8½ 39½ x 15½ -- ADA Height Requirement
  3612-RA Semi-Rec. 4 36 x 12 x 8 39½ x 15½ 37 x 13 x 4½ ADA Handle Requirement
FS 3612-RA Semi-Rec. 4 36 x 12 x 8 39½ x 15½ 381/8 x 141/8 x 53/8 ADA Handle Requirement
  M3216-R Rec. 5/16 32 x 16 x 8 35½ x 19½ 33 x 17 x 8¼ YES PW2½,MP20,
DC20,CD10,
CD15,WC-6L,
WM2½
FS M3216-R Rec. 5/16 32 x 16 x 8 35½ x 19½ 341/8 x 181/8 x 91/8 YES
  M3216-RK Semi-Rec. 1¼ 32 x 16 x 8 35½ x 19½ 33 x 17 x 7¼ YES
FS M3216-RK Semi-Rec. 1¼ 32 x 16 x 8 35½ x 19½ 341/8 x 181/8 x 81/8 YES
  M3216-RL Semi-Rec. 2½ 32 x 16 x 8 35½ x 19½ 33 x 17 x 6 YES
FS M3216-RL Semi-Rec. 2½ 32 x 16 x 8 35½ x 19½ 341/8 x 181/8 x 7 YES
  M3216-RM Semi-Rec. 4½ 32 x 16 x 8 35½ x 19½ 33 x 17 x 4 ADA Height Requirement
FS M3216-RM Semi-Rec. 4½ 32 x 16 x 8 35½ x 19½ 341/8 x 181/8 x 47/8 ADA Height Requirement
  M3216-RT Trimless 32 x 16 x 8 -- - - x - - x 8½ YES
  M3216-SM Surface Mtd. 35½ x 19½ x 8½ 35½ x 19½ -- ADA Height Requirement
  M3216-RA Semi-Rec. 4 32 x 16 x 8 35½ x 19½ 33 x 17 x 4½ ADA Handle Requirement
FS M3216-RA Semi-Rec. 4 32 x 16 x 8 35½ x 19½ 341/8 x 181/8 x 53/8 ADA Handle Requirement

Wall installations and trim projections

NOTE: "FS" models denote Larsen's "Flame-Shield" fire-rated cabinets. When specifying Larsen's "Flame-Shield" fire-rated cabinet option for the Architectural Series, refer to the dimension chart above on this page and select from the models with an "FS" prefix. For complete details see the "Flame-Shield" option.
*Inside box depth is 4½" when supplied with aluminum door and trim. The AL2409-5R has a 1¼" square trim.

Trimless cabinets must be installed before drywall because their plaster stops must be behind the drywall. Trimless are not recommended for block wall installation.

Deduct ¾" from H x W dimensions for cabinets with aluminum door and trim. This does not apply to "FS" fire-rated option.

To comply with ADA wall projection guidelines, this cabinet must be mounted with its leading edge at or below 27" from the finished floor.

To comply with ADA wall projection guidelines, this cabinet must be specified with Larsen's recessed handle.

Contact Larsen's Mfg. - Request More Info

If you would like us to contact you or provide more information please use the online form below. Please note we respect your privacy and will not distribute your information including email address to anyone else. Thank You!
Name: Additional comments or specific questions:
E-mail:
Phone (required):
More information about:
How did you find us?
Minneapolis Division
7421 Commerce Lane N.E., Minneapolis, MN 55432
Phone: (763) 571-1181    Toll Free: 1-800-527-7367
Fax: (763) 571-6900
Florida Division
3130 N.W. 17th St., Ft. Lauderdale, FL 33311
Phone: (954) 486-3325    Toll Free: 1-800-262-3473
Fax: (954) 486-3352

©1999-2007 Larsen's Manufacturing Company
Website Design and Hosting by www.ManagementSpecialties.com